What extensions can I make to a fire rated partition?

You may want to extend a tested fire performing partition build-up.

The following rules have been taken from the Extended field of application standard EN 15254-1: Lightweight Partitions.

 

Framing

Allowed Not Allowed
Increase stud gauge Decrease stud gauge
Decrease stud spacing Increase stud spacing
Increase stud depth Decrease stud depth
Increase stud width Decrease stud width
  Change shape of the stud profile
 
 

Boarding

Allowed Not Allowed
Increase thickness of board Swap boards
Increase the number of board layers Decrease the number of board layers
Increase the number of board layers while decreasing the thickness of board as long as the total lining thickness is more than that tested Swap board layers
Decrease board size (not thickness) Change the orientation of the boards
 
 

Insulation

Allowed Not Allowed
Increase thickness of insulation Add insulation to a non-insulated system
Swap glass mineral wool for stone wool insulation Remove insulation from an insulated system
Increase density of insulation Swap stone wool for glass mineral wool
 
 

 